10
RTU Mode:
To Read Instruction
To Read Response
Message
To Write Instruction
To Write Response
Message
Machine address
01H
01H
Machine
address
01H
01H
Machine
address
01H
01H
Machine
address
01H
01H
Instruction 03H
01H
Instruction 03H
01H
Instruction
06H
05H
Instruction 06H
05H
10H
08H
10H
08H
10H
08H
Starting address of
reading data
00H
10H
Response data
length (byte)
04H
02H
To write
data
address
01H
10H
To write data
address
01H
10H
00H
00H
01H
17H
03H
FFH
03H
FFH
(word/bit)
02H
09H
Data content 1
F4H
01H
To write
data
content
20H
00H
To write data
content
20H
00H
CRC low byte
C0H
BBH
03H
CRC low
byte
DDH
8FH
CRC low byte
DDH
8FH
CRC high byte
CBH
A9H
Data content 2
20H
CRC high
byte
E2H
9FH
CRC high byte
E2H
9FH
CRC low byte
BBH
77H
CRC high byte
15H
88H
CRC (Cyclical Redundancy Check) program example:
unsigned int reg_crc = 0xffff; i = 0;
while (length--)
{
reg_crc ^= RTUData[i];
i ++;
for (j = 0; j < 8; j++)
{
if (reg_crc & 0x01) reg_crc = (reg_crc >> 1) ^ 0xA001;
else reg_crc = reg_crc >> 1;
}
}
return (reg_crc);
11
INSTALLATION
SCD series can be extended up to 8 modules and installed by DIN rail mounting.
2
SCD unit
Mounting Panel
DIN rail
1
2
12
HOW TO SET UP CURRENT INPUT
For normal input
For current input (4 ~ 20mA, 0 ~ 20mA)
PIN HEADER
JP1
DEFAULT SETTING
PIN HEADER
JP1
Commenti su questo manuale